15

Figure

16

Rotational Limit Settings for 8394-04

Application

Rotation Limits

Stop Screw

Locations

45

°Left or Right of Straight Ahead

D & H


Aerial Ladder, Elevating
Platform, or Water Tower


90

°Left or Right of Straight Ahead

F

Deck Gun

174

°Left or Right of Straight Ahead

A

Table 3

Horizontal Settings for 8394-04

Application

Rotation Limits

Stop Screw

Locations

Aerial Ladder

or Deck Gun

90

° above horizontal to 45° below horizontal

T

Elevating Platform

45

° above horizontal to 45° below horizontal

T & U

Table 4

Vertical Settings for both 8294-04 and 8394-04


*The following paragraphs from NFPA 1901, 2003 Ed, specify minimum angles of rotation for
aerial device monitors:

1. Aerial Ladder Water Delivery System. (NFPA ¶16-6.1.1)

The monitor shall be capable of swiveling at least 135 degrees from a line parallel to
the ladder and down. The monitor shall be capable of horizontal traverse at least 45
degrees from each side of center.