ERICO EPD240TDAARB (240 Vac, 0-30A) Secondary Surge Protectors User Manual

Installation instructions, Secondary surge protectors, Series tvss filters

Advertising
background image

Secondary Surge Protectors

Series TVSS Filters

2003 ERICO

Inc, 34600 Solon Rd, Solon, OH 44139

Page 1 of 1

Document Number: HBCR1671 Revision: 1

EPD120TDAARB (120 Vac 0-30A)

EPD240TDAARB (240 Vac, 0-30A)

Installation Instructions

EPD

UNIT

L

G ( )

N

L

N

SENSITIVE

ELECTRONICS

SECONDARY
PROTECTOR

TWIST

WIRING

PRIMARY

PROTECTOR

LOAD CENTER OR

BREAKER BOX

5 3/4

4 3/4

5 1/4

3 1/2

2 3/8

2 3/8

2 3/8

3 1/2

AAR HARDWARE

SUPPLIED

MOUNTING SCREWS

SUPPLIED

FIG. 1

FIG. 2

FIG. 3

www.erico.com

= OK

ERICO PROTECTION DEVICES

R

TM

INPUT

N

INPUT

L

OUTPUT

L

OUTPUT

N

CAUTION! 30A MAX.

STATUS INDICATOR

DANGER: Electrical shock or burn hazard.
Installation of Secondary Surge Protector should be
made by qualified personnel. Failure to lockout

electrical power during installation or maintenance can
result in fatal electrocution or severe burns.

1. Disconnect and lockout power to the point where the

Secondary Surge Protector (EPD unit) is to be installed.
Follow all applicable electrical codes & procedures.

CAUTION: Check to make sure line voltage does
not exceed EPD unit voltage requirement. These
EPD units do not have overcurrent protection, and

should be fed from an appropriately sized breaker (<= 30A).

2. Mount the EPD unit as close as possible to the sensitive

electronics being protected. See FIG. 3.

3. For mounting, use layout of holes as indicated in FIG. 1;

drill 9/64 diameter holes in the mounting surface for the
#8 x 1/2-lg. screws provided.

4. Output wires should be kept as SHORT as possible

between equipment and the EPD unit, and the input and
output wires should be twisted to minimize noise
coupling.

5. Input and output wires to and from the EPD unit should

be separated to minimize noise coupling.

6. Use A.A.R. hardware supplied. See FIG. 2 for assembly.

7. The LED on the front panel illuminates to indicate that

the protection circuitry is operating correctly. If LED has
extinguished, the EPD unit has sustained a surge beyond
its ratings and the unit should be replaced immediately as
no protection may be provided.



8. Engage power to the EPD unit. Status LED should

illuminate indicating correct operation. If not, disconnect
power, check wiring, rectify any deficiencies, and reapply
power. If still experiencing difficulties, please contact
your supplier, or the manufacturer:

ERICO, Inc.
Rail Electrical Products
34600 Solon Rd
Solon OH 44139 USA
Ph. (800) 447-7245
Ph. (440) 542-3939