INSTALLING THE SENSOR

WIRING

STEP 2

Secure the

sensor on the bracket by

pressing it down into the

slotted hole as shown

above.

STEP 3

Using an extended wood

or masonry bit, drill a ¼" hole

through the side of the house at a

location giving the best access to

the boiler and the HydroStat control.
WARNING: Use caution to select

the hole location away from wires

or piping within the house wall.

STEP 4

Feed the sensor cable

through the hole and into the house.

Seal the hole with a bead of silicone

or other appropriate caulking

material.

STEP 5

Inside the house, route

the sensor cable to the HydroStat

control. Splice in an additional

length of wire as needed and, using

a crimping tool or pliers, terminate

with the two spade connectors pro-

vided.
NOTE: To avoid interference with

the sensor signal, do not run the

sensor cable close to any other

wiring such as telephone, cable,

power, etc.

Locate the three quick connect posts on the HydroStat

circuit board. The sensor cable will plug into two of

these terminals depending on the features to be used.

OUTDOOR RESET AND

WARM WEATHER SHUTDOWN

Attach the spade connectors to the right and

center spade posts (OR and C) for full outdoor reset

functionality including warm weather shutdown protec-

tion. Wiring this way overrides the Thermal Targeting

function of the Fuel Smart HydroStat control.

WARM WEATHER SHUTDOWN ONLY

Connect the wire ends to the left and center spade

connectors (WWSD and C) to add warm weather shut-

down functionality only. When wired this way, the Fuel

Smart HydroStat control will utilize its internal Thermal

Targeting function to reset the boiler temperature.

STEP 1

Using the

two screws and wire

clip provided, attach

the sensor bracket to

the side of the house.

Advertising