Technical data, General data and operating conditions, 4technical data – Lenze CS 9000 DVI Operating Instructions User Manual

Page 21

Advertising
background image

Technical data

General data and operating conditions

4

l

21

BA_CS9000DVI EN 4.0

4

Technical data

4.1

General data and operating conditions

General data

Conformity and approval

Conformity

CE

EN 61000−6−4
EN 61000−6−2

EMC Directive Class A, industrial premises

Approbation

UR

UL 508
CSA C22.2

Programmable Controllers (File−No. E236341)

Other

RoHS

Products lead−free in accordance with CE Directive
2011/65/EU

Protection of persons and equipment

Safety

VDE0805 (EN60950),
VDE0870, UL

Enclosure

Standard device

EN 60529

IP65

UL 508 (NEMA 250)

Type 1 enclosure pollution degree 2

Add−on components

EN 60529

IP65

Class of protection

3

EMC

Noise emission

EN 61000−6−4

Class A (industrial premises)

Noise immunity zone B

EN 61000−6−2

Industrial premises

EN 61000−4−2

ESD; severity level 3, i. e.
8 kV for air discharge,
4 kV for contact discharge

EN 61000−4−3

RF interference (housing)
80 MHz … 1000 MHz, 10 V/m 80 % AM (1 kHz)

EN 61000−4−4

Burst, severity level 3

EN 61000−4−5

Surge, severity level 1 *

EN 61000−4−6

RF cable−guided
150 kHz … 80 MHz, 10 V/m 80 % AM (1 kHz)

*

Due to the high−energy single current pulses, surges require suitable external wiring with lightning protection
elements like for example lightning conductors and overvoltage arresters.

Advertising
This manual is related to the following products: