Mechanical installation

Standard devices in a power range of 0.25 ... 3 kW

Mounting in ”cold plate” technique

5

103

EDS84ASC552 EN 9.1

5.2.3

Mounting in ”cold plate” technique

The E84AVxxC... controllers are designed for assembly on coolers (e.g. collective coolers) in

”cold-plate” technique.

Requirements for collective coolers
A good thermal connection to the cooler is important for the trouble-free operation of

the controller:

ƒ

The contact area between the collective cooler and the controller
– must be at least as big as the cooling plate of the controller.
– must be smooth, the maximum deviation must not exceed 0.05 mm.

ƒ

The collective cooler must be connected to the controller with all required screwed

joints.

ƒ

The thermal resistance R

th

must be observed, see table.

The values in the table apply to the operation of the controllers under rated

conditions.

The values include the heat transmission between the cooler and the device.

With a standard heat conducting paste and a film thickness of 50 m, the heat

transmission is approx.
– 0.03 K/W for controllers up to 5.5 kW
– 0.02 K/W for controllers up to 15 kW
– 0.01 K/W for controllers up to 22 kW.

Power to be dissipated

Thermal resistance

Type

P

v [W]

R

th

[K/W]

E84AVxxC2512

15

 1.5

E84AVxxC3712

20

 1.5

E84AVxxC5512

30

 1.0

E84AVxxC7512

40

 1.0

E84AVxxC1122

60

 0.6

E84AVxxC1522

75

 0.5

E84AVxxC2222

100

 0.4

E84AVxxC3714

25

 1.0

E84AVxxC5514

35

 1.0

E84AVxxC7514

50

 1.0

E84AVxxC1124

60

 0.6

E84AVxxC1524

70

 0.5

E84AVxxC2224

100

 0.4

E84AVxxC3024xxS

100

 0.4