Mechanical installation

Standard devices in a power range of 30 ... 45 kW

Mounting in ”cold plate” technique

5

148

EDS84ASC552 EN 9.1

5.4.2

Mounting in ”cold plate” technique

The E84AVxxC... controllers are designed for assembly on coolers (e.g. collective coolers) in

”cold-plate” technique.

Requirements for collective coolers
A good thermal connection to the cooler is important for the trouble-free operation of

the controller:

ƒ

The contact area between the collective cooler and the controller
– must be at least as big as the cooling plate of the controller.
– must be smooth, the maximum deviation must not exceed 0.05 mm.

ƒ

The collective cooler must be connected to the controller with all required screwed

joints.

ƒ

The thermal resistance R

th

must be observed, see table.

The values in the table apply to the operation of the controllers under rated

conditions.

The values include the heat transmission between the cooler and the device.

With a standard heat conducting paste and a film thickness of 50 m, the heat

transmission is approx. 0.007 K/W.

Power to be dissipated

Thermal resistance

Type

P

v [W]

R

th

[K/W]

E84AVxxC3034

720

 0.053

E84AVxxC3734

810

 0.047

E84AVxxC4534

1080

 0.035

Ambient conditions

ƒ

The rated data and the derating factors at increased temperature also apply to the

ambient temperature of the drive controllers.

ƒ

Temperature at the cooling plate of the drive controller: max. 75 °C.

Note!

Apply standard heat-conducting paste or heat-conducting foil onto cooler and

cooling plate before you bolt the controller onto the cooler.