Electrical installation

Important notes

Device protection

6

158

EDS84ASC552 EN 9.1

Range

Connection

Name

Explanation

Power

X100

Mains

Protective separation towards X101, X106 and all

control terminals

DC bus

X105

Motor
Brake resistor

X101

Relay contact

Protective separation towards X100, X105 and all

control terminals

X106

Motor temperature

Protective separation towards X100, X105 and X101

Isolation by basic insulation towards all control

terminals
Degree of insulation of thermal contact, PTC, or

cable can influence the isolation.

Control

X1

System bus (CANopen)

Isolation by functional insulation towards other

control terminals

X3

Analog IO

X4

Digital IO
24 V external supply

The degree of insulation of the voltage source

influences the degree of insulation of the controller.

X5

Digital inputs

Isolation by functional insulation towards other

control terminals

24 V external supply

The degree of insulation of the voltage source

influences the degree of insulation of the controller.

X6

Diagnostics

Isolation by functional insulation towards other

control terminals

X107

24 V brake supply

Isolation by basic insulation towards other control

terminals

MCI

Communication

Isolation by functional insulation towards other

control terminals

MMI

Memory

Control

additional connections TopLine:
X7

Resolver

Isolation by functional insulation towards other

control terminals

X8

Encoder

X10

Axis bus

6.1.2

Device protection

ƒ

In case of condensation, do not connect the controller to the mains voltage before

the moisture has evaporated completely.

ƒ

The controller must be protected by external fuses.

ƒ

Provide unused control inputs and outputs with terminal strips.