1 shielding, Shielding, Electrical installation – Lenze 8400 User Manual

Page 166

Advertising
background image

Electrical installation

Installation according to EMC (installation of a CE-typical drive system)

Shielding

6

166

EDS84ASC552 EN 9.1

6.2

Installation according to EMC (installation of a CE-typical drive system)

Design of the cables

ƒ

It is imperative to comply with the regulations concerning minimum cross-sections

of PE conductors. The cross-section of the PE conductor must be at least as large as

the cross-section of the power connections.

ƒ

The cables used must comply with the approvals required for the location (e.g. UL).

6.2.1

Shielding

Requirements

ƒ

The effectiveness of a shielded cable is reached by:
– Providing a good shield connection through large-surface shield contact.
– Using only braided shields with low shield resistance made of tin-plated or

nickel-plated copper braid.

– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.

Use system cables or shielded cables for these connections:

ƒ

Motor

ƒ

Feedback systems

ƒ

Motor holding brake (shielding is required when being integrated into the motor

cable; connection to optional motor brake control)

ƒ

Motor temperature monitoring

ƒ

Analog signals (inputs and outputs; single-sided shield connection to the controller)

ƒ

System bus (CANopen)

The following connections need not be shielded:

ƒ

24-V supply

ƒ

Digital signals (inputs and outputs).
– We recommend to use shielded cables for a cable length from approximately 5 m

on or in environments with strong interferences.

Connection system

ƒ

Connect the shield with a large surface and fix it with metal cable binders or a

conductive clamp.

ƒ

Connect the shield directly to the corresponding device shield sheet.
– If required, additionally connect the shield to the conductive and earthed

mounting plate in the control cabinet.

– If required, additionally connect the shield to the cable clamp rail.

Advertising