Electrical installation

Installation according to EMC (installation of a CE-typical drive system)

Control cables

6

170

EDS84ASC552 EN 9.1

6.2.4

Control cables

ƒ

Control cables must be shielded to minimise interference injections.

ƒ

For lengths of approx. 5 m and more, use only shielded cables for analog and digital

inputs and outputs. Under 5 m, unshielded but twisted cables may be used.

ƒ

Connect the shield correctly:
– The shield connections of the control cables must be at a distance of at least 50

mm from the shield connections of the motor cables and DC cables.

– Connect the shield of digital input and output cables at both ends.
– Connect the shield of analog input and output cables at one end (at the drive

controller).

ƒ

To achieve an optimum shielding effect (in case of very long cables, with high

interference) one shield end of analog input and output cables can be connected to

PE potential via a capacitor (e.g. 10 nF/250 V) (see sketch).

9300vec043

Fig. 6-4

Shielding of long, analog control cables