Installation according to EMC (installation of a CE-typical drive system)

Detecting and eliminating EMC interferences

6

175

EDS84ASC552 EN 9.1

6.2.7

Detecting and eliminating EMC interferences

Fault

Cause

Remedy

Interferences of analog

setpoints of your own or

other devices and

measuring systems

Unshielded motor cable

Use shielded motor cable

Shield contact is not extensive enough

Carry out optimal shielding as specified

Shield of the motor cable is interrupted

by terminal strips, switched, etc.

Separate components from other

component part with a minimum

distance of 100 mm

Use motor choke/motor filter

Install additional unshielded cables

inside the motor cable (e.g. for motor

temperature monitoring)

Install and shield additional cables

separately

Too long and unshielded cable ends of

the motor cable

Shorten unshielded cable ends to

maximally 40 mm

Conducted interference

level is exceeded on the

supply side

Terminal strips for the motor cable are

directly located next to the mains

terminals

Spatially separate the terminal strips for

the motor cable from main terminals

and other control terminals with a

minimum distance of 100 mm

Mounting plate varnished

Optimise PE connection:

Remove varnish

Use zinc-coated mounting plate

HF short circuit

Check cable routing