3 residual hazards, Safety instructions – Lenze 8400 User Manual

Page 18

Advertising
background image

Safety instructions

Residual hazards

2

18

EDS84ASC552 EN 9.1

2.3

Residual hazards

Protection of persons

ƒ

Before working on the controller, check that no voltage is applied to the power

terminals, because
– depending on the controller - the power terminals U, V, W, +UG, -UG, Rb1 and Rb2

carry hazardous voltages for up to 3 to 20 minutes after mains disconnection.

– the power terminals L1, L2, L3; U, V, W, +UG, -UG, Rb1 and Rb2 carry hazardous

voltages when the motor is stopped.

Device protection

ƒ

Connect/disconnect all pluggable terminals only in deenergised condition!

ƒ

Detach the controllers from the installation, e.g. from the rear panel of the control

cabinet, only in deenergised condition!

Motor protection

ƒ

Depending on the controller settings, the connected motor can be overheated by:
– For instance, longer DC-braking operations.
– Longer operation of self-ventilated motors at low speed.

Protection of the machine/system

ƒ

Drives can reach dangerous overspeeds (e.g. setting of high output frequencies in

connection with motors and machines unsuitable for such conditions):
– The controllers do not offer any protection against such operating conditions. Use

additional components for this purpose.

ƒ

Switch contactors in the motor cable only if the controller is inhibited.
When switching contactors in the motor cable while the controller is enabled, you can

activate monitoring functions of the controller. If no monitoring function is activated,

switching is permissible.

Parameter set transfer

ƒ

During the parameter set transfer, control terminals of the controllers can adopt

undefined states!
– Therefore, it is absolutely necessary to remove control terminal X4 (digital input

signals for devices of the StateLine C version) or control terminal X5 (digital input

signals for devices of the HighLine C/TopLine C version). This ensures that the

controller is inhibited and all control terminals have the firmly defined ”LOW”

status.