background image

Electrical installation

StateLine C control terminals

Digital inputs and outputs

6

226

EDS84ASC552 EN 9.1

6.7.3

Digital inputs and outputs

X4

24 V int.

50

mA

24E

DI1

DI2

DI3

DI4

RFR

DC 24 V
(+19.2...
+28.8 V)

S1

3.3k

X4

GND-IO

DO1

GIO

24I

GND-IO

3.3k

3.3k

3.3k

3.3k

50

mA

8400SLC044

8400SLC045

Fig. 6-36

Connection of the digital inputs and outputs

Labelling

Description

RFR

Controller enable/controller inhibit, always required

DI1

Digital input 1

 79

IEC61131-2, type 1 or two-track frequency input, for

HTL encoding 0 ... 10 kHz

track A

DI2

Digital input 2

track B

DI3

Digital input 3

 79

DI4

Digital input 4

DO1

Digital output 1

 79

GIO

GND digital signals

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 1.5

24 ... 16

-

-

-

With wire end ferrule