3 digital inputs and outputs, Digital inputs and outputs, Electrical installation – Lenze 8400 User Manual

Page 233

Advertising
background image

Electrical installation

HighLine C control terminals

Digital inputs and outputs

6

233

EDS84ASC552 EN 9.1

6.8.3

Digital inputs and outputs

X5

24 V int.

50

mA

24E

DI1

DI2

DI3

DI4

RFR

DC 24 V

(+19.2...
+28.8 V)

S1

2.7k

2.7k

3.3k

3.3k

3.3k

X5

GND-I

DI5

DI6

DI7

GI

24I

1.6k

1.6k

3.3k

8400HLC036

8400HLC045

Fig. 6-42

Connection of the digital inputs

Labelling

Description

RFR

Controller enable/controller inhibit, always required

DI1

Digital input 1

 82

IEC61131-2, type 1 or two-track frequency input, for HTL

encoder 0 ... 200 kHz

track A

DI2

Digital input 2

track B

DI3

Digital input 3

 82

IEC61131-2, type 1

DI4

Digital input 4

DI5

Digital input 5

DI6

Digital input 6

IEC61131-2, type 1 or

two-track frequency input for HTL encoder 0 ... 10 kHz

DI7

Digital input 7

GI

GND digital inputs

Terminal data

Conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

0.2 ... 1.5

24 ... 16

-

-

-

With wire end ferrule

Advertising