1 keypad control, Keypad control, Commissioning – Lenze 8400 User Manual

Page 245: Quick commissioning keypad control, Highline/topline, Load lenze setting to controller

Advertising
background image

Commissioning

Quick commissioning

Keypad control

7

245

EDS84ASC552 EN 9.1

7.2.1

Keypad control

Commissioning steps
1. Wiring of power terminals
Consultthe”Electrical installation” chapterorthemountinginstructions towirethepower

connections according to the requirements of your device.
2. Wiring of control terminals.

– StateLine

Digital inputs at terminal X4

Assignment

Information

24E

DI1

DI2

DI3

DI4

RFR

X4

DO1

GIO

24I

RFR

Controller enable

RFR = High

Reset error

High  Low (edge-controlled)

– HighLine/TopLine

Digital inputs at terminal X5

Assignment

Information

24E

DI1

DI2

DI3

DI4

RFR

X5

DI5

DI6

DI7

GI

24I

RFR

Controller enable

RFR = High

Reset error

High  Low (edge-controlled)

3. Load Lenze setting to controller

Note!

The application ”actuating drive speed” is implemented with the Lenze

setting.

MCTRL: Act. speed val.

C00051

0 rpm

After attaching the keypad or

switching on the controller with

keypad attached, the connection

between keypad and controller is

established.

The connection has been established

when the code C00051 appears in

the display.

Then press the left function key.

SAVE

Par1 8400 StateLineC

User - Menu
Code list

Quick commissioning

SAVE

Par1 Quick commissioning

Terminals

Keypad

EDIT

Load Lenze setting

C00002/1

Starting from ”User menu” scroll

down with button to ”Quick

commissioning” menu

Click right button.

Select ”Keypad” menu.

Click right button.

Code 00002/1:

– Parameterise with left ”Edit”

function key

– Select value ”1”- -> On/Start

and confirm with right ”OK”

function key.