2 braking operation with external brake resistor, 1 operation at rated mains voltage 230 v, Operation at rated mains voltage 230 v – Lenze 8400 User Manual

Page 250: Braking operation

Advertising
background image

Braking operation

Braking operation with external brake resistor

Operation at rated mains voltage 230 V

8

250

EDS84ASC552 EN 9.1

8.2

Braking operation with external brake resistor

To decelerate greater moments of inertia or with a longer operation in generator mode an

external brake resistor is required. It converts braking energy into heat.
The brake resistor is connected if the DC-bus voltage exceeds the switching threshold. This

prevents the controller from setting pulse inhibit through the ”Overvoltage” fault and the

drive from coasting. The external brake resistor serves to control the braking process at any

time.
The brake chopper integrated in the controller connects the external brake resistor.

ƒ

Adapt the switching threshold to the mains voltage (C00173/C00714, see software

manual).

Note!

DC-bus system without the use of a regenerative module:

ƒ

Up to and including software version V02.xx.xx, only an internal brake

chopper can be used in the DC-bus system to dissipate the regenerative

energy.

ƒ

Starting from software version V12.00.00, all internal brake choppers can be

used in the DC-bus system to dissipate regenerative energy (”master-slave

operation”).
More information can be found in the ”Braking operation/brake energy

management” chapter of the reference manual.

8.2.1

Operation at rated mains voltage 230 V

Switching threshold V

BRmax

: 380 V, adjustable

R

Bmin

[]

I

BRmax

[A]

P

BRmax

[kW]

I

BRd

[A]

P

Bd

[kW]

t

Z

[s]

t

on

[s]

t

fp

[s]

Type
E84AVxxx2512

180

2.1

0.8

1.6

0.6

-

-

E84AVxxx3712

180

2.1

0.8

1.6

0.6

-

-

E84AVxxx5512

100

3.8

1.4

2.8

1.1

-

-

E84AVxxx7512

100

3.8

1.4

2.8

1.1

-

-

E84AVxxx1122

33

11.5

4.4

8.6

3.3

-

-

E84AVxxx1522

33

11.5

4.4

8.6

3.3

-

-

E84AVxxx2222

33

11.5

4.4

8.6

3.3

-

-

R

Bmin

Minimum brake resistance, nominal value ±10 %

I

BRmax

Peak current

P

BRmax

Peak braking power

I

BRd

Continuous current RMS - important for the dimensioning of the cables

P

Bd

Continuous braking power

t

Z

Cycle time, periodic load change with running time and recovery time

t

on

Running time

t

Z

- t

on

Recovery time

t

fp

Maximum running time without initial load and compliance with the recovery

time