background image

Technical data

General data and operating conditions

4

27

EDS84ASC552 EN 9.1

4

Technical data

4.1

General data and operating conditions

Conformity and approval
Conformity

CE

2006/95/EC

Low-Voltage Directive

Approval

UL

UL 508C

Device size 1 ... 7 (0.25 ... 45 kW)

Certification of the integrated safety system: see chapter

10.9

CSA

CSA 22.2 No. 14

Device size 1 ... 7 (0.25 ... 45 kW)

Only if an external mains choke is used.

Protection of persons and device protection
Type of protection

EN 60529

IP 20  183

Specification

applies to the fully

assembled state ready

for use

does not apply to the

wire range of the

terminals

NEMA 250

Protection against accidental

contact acc. to type 1

Insulation resistance

EN 61800-5-1

Overvoltage category III

Above 2000 m amsl: Overvoltage category II

Control circuit isolation

EN 61800-5-1

Safe mains isolation via double / reinforced insulation for

star-point earthed mains with a rated voltage for external

conductors / star point of up to 300 V.

Short-circuit strength

Earth-fault strength

EN 61800-5-1

Motor connection: Limited, i.e. an internal protective device

responds, the controller is inhibited

(Error acknowledgement is required)

Control terminals: Without limitation

Protective measures

against

Short circuit

Earth fault

(Earth fault strength depends on the operating status)

Overvoltage

Motor stalling

Motor overtemperature

(PTC or thermal contact, I

2

t-monitoring)

Leakage current

EN 61800-5-1

> 3.5 mA AC, > 10 mA DC

Observe regulations and

safety instructions!

Mains switching

Mains switching 3 times in 9 minutes (without

restrictions)

More frequent mains switching, e.g. during setting-up

operation, does not harm the controller.

– Devices of up to 22 kW are protected against overload.

A monitoring issues the ”Su03” message. The message

must be acknowledged via mains switching. Before you

switch on again: Let the device cool down!

– Devices from 30 kW are protected by the dimensioning

of the load circuit. Monitoring is not carried out.

Starting current

 2 x I

rated