Technical data

Rated data

Operation at rated mains voltage 230 V

4

36

EDS84ASC552 EN 9.1

4.2.2

Operation at rated mains voltage 230 V

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

1/N/PE AC

230

180 - 0 % ... 264 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Apparent output power

Motor power

with external

mains choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LR

[A]

I

LR

[A]

S

aR

[kVA]

P

aR

[kW]

E84AVxxx2512

3.0

3.4

0.6

0.25

E84AVxxx3712

4.2

5.0

0.9

0.37

E84AVxxx5512

5.0

5.3

1.1

0.55

E84AVxxx7512

7.0

8.0

1.4

0.75

E84AVxxx1122

9.9

12.0

2.0

1.1

E84AVxxx1522

11.4

13.7

2.5

1.5

E84AVxxx2222

16.4

21.8

3.4

2.2

Assignment of external mains chokes

Assignment
Type

Mains choke required

Mains choke

E84AVxxx2512

No

ELN1-0900H005

E84AVxxx3712

No

E84AVxxx5512

No

ELN1-0500H009

E84AVxxx7512

No

E84AVxxx1122

No

ELN1-0250H018

E84AVxxx1522

No

E84AVxxx2222

No

Advertising