Technical data

Rated data

Operation at rated mains voltage 400 V

4

40

EDS84ASC552 EN 9.1

4.2.3

Operation at rated mains voltage 400 V

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

400

320 - 0 % ... 440 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Apparent output power

Motor power

with external

mains choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LR

[A]

I

LR

[A]

S

aR

[kVA]

P

aR

[kW]

E84AVxxx3714

1.4

1.8

0.8

0.37

E84AVxxx5514

2.2

2.7

1.1

0.55

E84AVxxx7514

2.5

3.6

1.5

0.75

E84AVxxx1124

3.2

4.4

2.0

1.1

E84AVxxx1524

3.9

5.5

2.4

1.5

E84AVxxx2224

5.1

7.3

3.5

2.2

E84AVxxx3024xxS

7.0

9.8

4.6

3.0

E84AVxxx3024xx0

7.0

9.8

4.6

3.0

E84AVxxx4024

8.8

13.1

5.9

4.0

E84AVxxx5524

12.0

18

8.1

5.5

E84AVxxx7524

15.0

20.0

10.3

7.5

E84AVxxx1134

21.0

29.0

14.7

11.0

E84AVxxx1534

1)

29.0

-

20.0

15.0

E84AVxxx1834

36.0

50.4

24.9

18.5

E84AVxxx2234

1)

42.0

-

29.3

22.0

E84AVxxx3034

1)

55.0

-

38.0

30.0

E84AVxxx3734

1)

68.0

-

47.4

37.0

E84AVxxx4534

1)

80.0

-

55.5

45.0

1)