4 operation at a rated mains voltage of 500 v, Operation at a rated mains voltage of 500 v, Technical data – Lenze 8400 User Manual

Page 47

Advertising
background image

Technical data

Rated data

Operation at a rated mains voltage of 500 V

4

47

EDS84ASC552 EN 9.1

4.2.4

Operation at a rated mains voltage of 500 V

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

3/PE AC

500

400 - 0 % ... 550 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Apparent output power

Motor power

with external

mains choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LR

[A]

I

LR

[A]

S

aR

[kVA]

P

aR

[kW]

E84AVxxx3714

1.1

1.4

0.8

0.37

E84AVxxx5514

1.7

2.2

1.1

0.55

E84AVxxx7514

2.0

2.9

1.5

0.75

E84AVxxx1124

2.6

3.6

2.0

1.1

E84AVxxx1524

3.1

4.4

2.4

1.5

E84AVxxx2224

4.1

5.8

3.5

2.2

E84AVxxx3024xxS

5.6

7.8

4.5

3.0

E84AVxxx3024xx0

5.6

7.8

4.5

3.0

E84AVxxx4024

7.0

10.5

5.9

4.0

E84AVxxx5524

9.6

14.4

8.1

5.5

E84AVxxx7524

12.0

16.0

10.3

7.5

E84AVxxx1134

16.8

23.2

14.7

11.0

E84AVxxx1534

1)

23.2

-

20.0

15.0

E84AVxxx1834

31.0

43.4

26.1

18.5

E84AVxxx2234

1)

36.1

-

31.5

22.0

E84AVxxx3034

1)

46.9

-

40.5

30.0

E84AVxxx3734

1)

58.2

-

50.7

37.0

E84AVxxx4534

1)

69.2

-

60.0

45.0

1)

only with external mains choke

Advertising
This manual is related to the following products: