4 digital inputs, 5 digital outputs, 6 connection of relay output – Lenze 8400 User Manual

Page 82: Digital inputs, Digital outputs, Connection of relay output, Technical data

Advertising
background image

Technical data

HighLine C control terminals

Digital inputs

4

82

EDS84ASC552 EN 9.1

4.7.4

Digital inputs

Labelling

Features

Rated value

X5/DI1, DI2

Digital input 1/2

according to IEC61131-2, type 1

or

two-track frequency input for HTL encoder 0 ... 200 kHz

X5/DI3, DI4, DI5 Digital input 3/4/5

according to IEC61131-2, type 1

X5/DI6, DI7

Digital input 6/7

according to IEC61131-2, type 1

or

two-track frequency input for HTL encoder 0 ... 10 kHz

X5/RFR

Controller inhibit

according to IEC61131-2, type 1

Input resistance

3.3 k (2.5 k ... 6 k)

Electric strength of external

voltage

Up to ±30 V, permanent

Level

LOW < +5V

HIGH > +15V

Cycle time

1 ms, can be changed by software filtering

Isolation

 157

X5/GI

GND, reference potential for digital signals

4.7.5

Digital outputs

Labelling

Features

Rated value

X4/DO1, DO2,

DO3

Digital output 1/2/3 - for operation of the

digital outputs an external voltage source is

required ( 80)

In accordance with IEC61131-2, type 1, max.

50 mA

External-voltage protected

Up to +30 V

Isolation

 157

Level

LOW < +5 V

High > +15 V

Time-dependent behaviour

LOW - HIGH / HIGH - LOW

Max. 250 s

Overload behaviour

Reduced voltage or periodical switch-off/on

Reset and switch-on behaviour

Outputs are switched off (LOW)

Cycle time

1 ms

X4/GO

GND, reference potential for digital signals

4.7.6

Connection of relay output

Labelling

Description/features

Rated value

X101 In the Lenze setting, the relay switches if the controller changes to the ”Fault” device status.

Observe the notes provided in the corresponding software manual if you would like to implement

parameters other than envisaged in the Lenze setting.
COM

Relay centre contact

AC 250 V, 3 A

DC 24 V, 2 A

DC 240 V, 0.16 A

According to UL508C:

– 3 A, 250 V AC (general purpose)

– 2 A, 24 V DC (resistive)

NC

NC contact (normally closed)

NO

NO contact (normally open)

Advertising
This manual is related to the following products: