Technical data

HighLine C control terminals

Motor holding brake connection

4

83

EDS84ASC552 EN 9.1

4.7.7

Motor holding brake connection

Labelling

Feature

Rated value

X107/24B

X107/GB

Connection for external 24 V supply voltage

by a safely separated power supply unit

(required for the supply of the brake output)

24 V in accordance with IEC 61131-2

19.2 ... 28.8 V

Residual ripple max. 

SELV/PELV

Suppression of voltage pulses

Suppressor diode 36 V, bidirectional

Polarity reversal protection

No

Rated current

2.5 A DC

Capacity to be charged

1 F

X107/BD1

X107/BD2

24 V voltage output for connecting a motor

holding brake via potential-free contacts

The brake output can also be used as a

potential-free, digital output that can

exceed a certain current value, e.g. for

switching a relay or valve.

Max. output current

2.5 A

Max. voltage drop in the high state

< 3 V for rated current

Breaking energy

Max. 5 Ws

Isolation

Basic insulation ( 157)

Level

LOW < +5 V

High > +15 V

Time-dependent behaviour

LOW - HIGH / HIGH - LOW

Max. 500s

Behaviour during overload

Reduced voltage or periodic switch-off/on

Reset and switch-on behaviour

Outputs are switched off

Cycle time

1 ms

Operating frequency

Max. 6/min for max. breaking energy