3 resolver connection, Resolver connection, Technical data – Lenze 8400 User Manual

Page 87

Advertising
background image

Technical data

TopLine C control terminals

Resolver connection

4

87

EDS84ASC552 EN 9.1

4.8.3

Resolver connection

Resolvers are connected to X7 (9-pole Sub-D socket).
To avoid interference injection, only use shielded motor and encoder cables if an encoder

is used.
You can connect and operate:

ƒ

Resolvers
– Parameterisation of the number of pole pairs in C00925
– Lenze setting: Number of pole pairs = 1.

ƒ

Multipole resolvers with a number of resolver pole pairs  2

ƒ

Resolvers of other manufacturers

Please ensure compliance with the technical limiting values of the resolver:

Description

Rated value

Cable length (system cable is recommended)

Max. 150 m

Number of resolver pole pairs

1 ... n

Carrier frequency of the excitation voltage

4 kHz

Impedance

Z

RO

= (R

RO

+ j X

RO

) = 90.9 Ohms (max.)

When a resolver with a lower rotor impedance (Z

RO

) is

connected, the integrated overload protection limits the

excitation current which impairs the signal quality and

may distort the determined actual values.

X7 /
Pin 1, 2

+REF, -REF
Excitation voltage

R.m.s. value: V = 7.07 V

Peak value: û = 10 V

Maximum excitation current

R.m.s. value: I = 77.78 mA

Peak value: Î = 110 mA

Pin 4, 5

+COS, -COS

Pin 6, 7

+SIN, -SIN

Pin 8, 9

+KTY, -KTY

Type: KTY 83-110, KTY 84, adjustable