Lowell ULT SERIES User Manual

Installation sheet #is-ult, Listed, Lowell manufacturing company

Advertising
background image

ULP625X ENCLOSURE

ULTSG4CT572

ASSEMBLY

INSTALLATION SHEET #IS-ULT

ULT Series 4" Speaker Assemblies

for Fire Protective Signaling

Installation - Series ULT (28LO) Fire Protective Signaling Speaker

These speakers are intended to be employed in either of the following configurations:

B. For general (non-fire alarm) signaling service in conjunction with compatible Listed sound
recording and reproducing equipment, the combination of which is intended to be installed in
accordance with the applicable requirements of the National Electrical Code and the local
authorities having jurisdiction. The amplifier or other sound reproducing equipment provides the
power for voice communication or any other related function to the speakers.

Connection Notes: Parallel input leads are provided on Series ULT speakers for proper utilization
of the electrical supervision scheme. Connect one pair (red and black) to the incoming line from
the signal source or previous speaker. Connect the other pair (red and black) to the outgoing line
to the next speaker or end-of-line termination device. A red jumper is connected to the 70.7V 0.5W
tap when shipped from the factory. If desired, move the red jumper to a different transformer power
tap lug. See "Figure 1" on this page for available transformer power taps.

Instruction Sheet:

IS-ULT P/N 13244

Page 1 of 1

Printed in U.S.A. 2-12-10

Lowell Manufacturing Company

100 Integram Drive

Pacific, Missouri 63069 U.S.A.

Call: 800-325-9660

Fax: 636-257-6606

Click: www.lowellmfg.com

ULCP4 ENCLOSURE

ULCB44 ENCLOSURE

ELECTRICAL SPECIFICATIONS

Frequency Response: 60Hz - 12kHz + 9dB

Intended Use: Indoor Dry Locations

JR410 Driver Size: 4" (EIA 5")

JR410 Driver Power Rating: 15 watts RMS

Supervision Capacitor: 10uF 160V. Maximum Allowable Supervision Voltage: 100 VDC.

JR410 Magnet: 10 oz. Ceramic

JR410 Impedance: 8 Ohms

2kHz Dispersion at -6dB down points: With SG4 Grille:120 Degrees/With WB4 Grille:110 Degrees

JR410 Driver Construction: Paper Cone, 1" Voice Coil, 20 Gauge Stamped Steel Basket

ULTWB4CT572

ASSEMBLY

FRONT VIEW

70V-5W

70V-2W

25V-0.25W

70V-1W

25V-5W

25V-2W

25V-1W

REAR VIEW

25V-0.5W

70V-0.5W

70V-0.25W

70/25V COM

8 OHM

SPKR COM

FIGURE 1

#13456

TRANSFORMER TAPS

MAXIMUM

VOLTAGE

TLM572 (#13456)

TRANSFORMER TAP

UL dBA RATING AT 10FT

5.0 W.

2.0 W.

1.0 W.

0.5 W.

0.25 W.

0.25 W.

0.5 W.

1.0 W.

2.0 W.

5.0 W.

ULTWB4CT572

ULTSG4CT572

75.6

ELECTRICAL AND AUDIBLE RATINGS

70.7 V

RMS

25 V

RMS

UL dBA RATING AT 10FT

82.9

79.7

76.9

60.0

82.7

80.2

77.2

60.2

75.6

82.9

79.7

76.9

60.0

77.9

82.7

80.2

77.2

60.2

77.9

Note: The UL dBA ratings given above are the low readings from 11 samples so they may not be as expected for one sample.

Directional Characteristics Test With Full Power Pink Noise Input Measured at 3m:
On Axis = 92.2dBA, -3dBA at 50

o

off axis, -6dBA at 70

o

degrees off axis, 83.0dBA at 90

o

off axis

A. For fire alarm signaling service in conjunction with a compatible Listed system control unit, the
combination of which is intended to be installed as a combination system control in accordance
with the applicable requirements of NFPA 72 and the local authorities having jurisdiction. The
amplifier, in conjunction with the tone generator located in the control unit, provides the power and
signal, either for the alarm evacuation and/or for voice communication.

FIRE ALARM

EQUIPMENT

28LO

SIGNALING

LISTED

UL

R

Advertising
Table of contents