There are inherent dangers associated with electrical products. Failure to follow

safety precautions can result in serious injury or death. These instructions must

be followed to ensure the safe and proper installation, operation and

maintenance of the Meltric devices. Before installation, disconnect all sources of

power to the circuit to eliminate the risk of electrical shock

.

RATINGS:

1 - 50 Volts DC - May be made and broken under load without pilot circuit.

50 - 600 Volts DC - Requires a pilot circuit to prevent disconnection under load.

DANGER: This device is not intended to be broken under load without the use of a pilot

control circuit. For operations over 50VDC, a control circuit must be used using the pilot

and ground to safely prevent unintended current interruption by the device. Failure to

follow proper usage will result in serious injury or death.

200A maximum with correct conductor size.

INSTALLATION:

Wire sizes: 4 AWG to 4/0 AWG - Phases; 6 AWG - Earth; 8 AWG - Pilot

Indoor Use; Outdoor use when used with 50 Volts or less and rubber boots

Configurations: 2P + E + Pilot, 2P + E

Colors: Black and Grey (Note: Black plug mates with grey receptacle, but grey plug mates

only with grey receptacle).
1. Insure that wire and device rating is suitable for the application. NOTICE: The use of undersize

wire may result in product failure due to excessive heat.

2. Remove contacts from plug or receptacle by removing the plastic covered or metal screws on

the bottom of the device. If the screws will not fall free after loosening, strike the device on a

suitable surface to remove them.