Alpha Controller

Configuration with STE-8000 Series

1

POWER ON

- The LCD will display the room temperature.


CHANGING SETPOINT - Press SETPOINT once to select COOLING OCCUPIED SETPOINT.

- Press UP/DOWN to change numerical value.

- Press SETPOINT again to select HEATING OCCUPIED SETPOINT.

- Press SETPOINT to return to Room temperature display.


CONTROLLER

- Press and hold both UP & DOWN arrows for 5 seconds to enter into the CONFG MENUS

CONFIGURATION
MENUS

** Refer to the Titus STE-8001 installation guide for additional details **

The Titus APLHA Controller can be programmed in three different ways:

-

Factory Set Up

-

BAS/ Computer thru BACnet network with an additional router.

-

STE- 8000 Series Thermostat (see below)

The Titus STE-8001 series thermostat has (3) buttons:

-

UP / DOWN, and SETPOINT

-

The flow chart on the following pages is intended to simplify the
calibration procedure.

-

Please note that a Level 1 password is required to change the set-point
temperature on the thermostat and a Level 2 password is required for
commissioning.