Q-Frame Circuit Breaker

Instruction Leaflet for Installation of Q-Frame Circuit Breakers

WARNING

CONTACT WITH ENERGIZED EQUIPMENT CAN
RESULT IN DEATH, SEVERE PERSONAL INJURY,

OR

SUBSTANTIAL PROPERTY DAMAGE. DO NOT

NANCE ON EQUIPMENT WHILE IT

IS ENERGIZED.

ALWAYS VERIFY THAT NO VOLTAGE

IS PRESENT

BEFORE PROCEEDING WITH THE TASK, AND

ALWAYS FOLLOW GENERALLY ACCEPTED SAFETY

PROCEDURES.

ATTEMPT TO INSTALL

OR PERFORM MAINTE-

ALLEN-BRADLEY

IS NOT LIABLE FOR THE MISAP-

PLICATION

OR

OF ITS

PRODUCTS.

The user is cautioned to observe all recommendations,
warnings, and cautions relating to the safety of personnel
and equipment as well as all general and local health and
safety laws, codes, and procedures. The recommenda-
tions and information contained herein are based on

Allen-Bradley experience and judgement, but should not
be considered to be

or covering every appli-

cation or circumstance which may arise. If any questions

Fig. 1-1 Q-Frame Circuit Breaker

Frame with Trip Unit Installed

arise, contact Allen-Bradley for further information or

instructions.

1.

INTRODUCTION

General Information

The Q-Frame circuit breaker (Fig. 1-1)

are 600 Vac maximum rated devices with
interchangeable thermal-magnetic or electronic

trip units rated 600A maximum continuous
current. The circuit breaker uses noninterchanageable
trip units and is factory sealed.

Refer to Table 1-1 for all available trip unit ratings.

This instruction leaflet (IL) gives procedures for installa-
tion and field testing of Q-Frame circuit breakers.

For this publication, the term circuit breaker shall also
include the molded case switch.

100 Percent Rated L-Frame Circuit Breakers

Q-Frame circuit breakers are suitable for conrtinuous
operation at 100 percent of the frame rating

if

used with 90°C insulated wire and AL9CU terminals in an

enclosure which measures at least 24" high x 15" wide x
6" deep. The minimum required ventilation is 8 sq. in. top
front and 8 sq. in. bottom front.

2.

INSTALLATION

The installation procedure consists of inspecting the cir-
cuit breaker and, as applicable, installing the trip unit and

rating plug, accessories, and terminals; mounting the cir-

cuit breaker; connecting the line and load conductors;
torquing terminals; and attaching terminal shields. Circuit
breaker frames, trip units, rating plugs, accessories,

mounting hardware, and unmounted terminals may be

Bul. 140U

40752-078(1)

Effective 5/02

supplied in separate packages. To install the circuit
breaker, perform the following steps.