Rockwell Automation 1492-CM800-LD005 Field Wire Conversion Module for Modicon B807-132 to 1756-IA32 User Manual

Rockwell Automation Equipment

Advertising
background image

Field Wire Conversion Module for Modicon B807-132 to 1756-IA32
(Cat 1492-CM800-LD005)

10000021868

(Version 00)

Printed in Germany

Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com.
In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog
Number and in the Search box type in the catalog number of the conversion system component.

I. Module Description

The 1492-CM800-LD005 conversion module provides field wire signal conversion from a Modicon® B807-132, 80 to
130Vac , 32-pt input module to a ControLogix 1756-IA32, 74 to 132Vac , 32-pt input module. The conversion
module provides the mating connections to the B807-132 swing-arm (terminal block) with the attached field wires. It
routes those signals, via its 40-pin connector and a 1492-CABLEZ pre-wired cable to compatible terminals of the
1756-IA32 module (refer to the Wiring Diagram on pages 2 and 3).

II. Module Installation

The 1492-CM800-LD005 conversion module must be installed in a 1492 conversion base-plate and cover-plate
assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the
conversion assembly. For a list of compatible assemblies refer to Appendix A.

III. Conversion Module Compatibility Matrix

Refer to conversion module Specifications Section: Maximum Operating Voltage

This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable

length is 003 (00.3 meters).

Conversion Module

Compatible 800

Input Module

Compatible 1756

Input Module

Required 1492 Cable

1492-CM800-LD005

B807-132

1756-IA32

1492-CABLEZ

40-pin connector for 1492-CABLEZ

Mating connector for
B800 Terminal Block

1492-CM800-LD005 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING