Rockwell Automation 1102C-COx93_DOx93 Vacuum Contactor (400A / 600A) User Manual

Inspection - unpacking, E - doc

Advertising
background image

Inspection

page 1

Installation

page 2

Coil Replacement

page 2, 3

Control Pak Replacement

page 4

Aux. Contact Assembly Installation

page 4

Vacuum Interrupter Phase Assembly Replacement

page 4, 5

Contact Life Over-Travel Measurement

page 5

Cleaning and Maintenance

page 6

Vacuum Interrupter Integrity Test

page 6

Wiring

page 6

Dimensions

page 7

Replacement Parts

page 8

ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.

Inspection - Unpacking

Before the contactor is placed in service, check carefully for shipping damage. Any damage should be reported to the carrier within (3)
three days of receipt. For overseas deliveries, it is important to obtain a certificate of examination from the nearest insurance inspector and
photographs of the damage. This and other evidence should accompany any communication to the insurance company or shippers. In the
event equipment is to be returned to the factory, contact Allen-Bradley Customer Service Department or our local A-B Distributor for return
authorization. A returned material authorization (RMA) number will be issued which should appear on all correspondence and the returned
container.
The Bulletin 1102C Vacuum Contactor is shipped in a shock resistant filled cardboard box. The following steps should be taken when
unpacking the contactor:

1. Check the packing list against the order to make sure the shipment is complete and components are received.

2. Examine the shipping box before unpacking the contactor to make sure it has not been damaged in shipment. If the shipping box is
damaged, pay particular attention when unpacking to see if the contents are also damaged. Notify the carrier if damage is found and notify
your local Allen-Bradley order field sales office of damage.

42052-080

G. Ushakow

N/A

N/A

N/A

42052

1006490

1

INSTRUCTION SHEET

BULLETIN 1102C VACUUM CONTACTOR

CURRENT RATINGS 400A AND 600A

200V-1500V

2-20-04

Mark Jutz

2-20-04

D. Josef

2-20-04

1

9

42052-104

REVISION

AUTHORIZATION

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

H

A

B

C

D

E

F

G

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

REFERENCE

SHEET

OF

DWG.

B

DR.

CHKD.

APPD.

DATE

DATE

DATE

±

±
±

ANGLES:

.XXX:

.XX:

THIS DRAWING IS THE PROPERTY OF

THE ALLEN-BRADLEY CO. INC.

AND MAY NOT BE COPIED, USED OR

DISCLOSED FOR ANY PURPOSE EXCEPT

AS AUTHORIZED IN WRITING BY

THE ALLEN-BRADLEY CO. INC.

LOCATION : MILWAUKEE,

WISCONSIN

U.S.A.

SIZE

1

2

3

4

5

6

7

8

E - DOC

Bulletin 1102C Vacuum Contactor Maintenance and

Installation Instructions (Current Ratings 400A and 600A -- 200V-1500V)

(Cat 1102C-CO_93 -- 400A, 3 Pole Contactor - 1500V Max)
(Cat 1102C-DO_93 -- 600A, 3 Pole Contactor - 1500V Max)

VACUUM

CO

NTA

CTO

R

VAC

UUM

CON

TAC

TOR

Vacuum Contactor - 400A

Vacuum Contactor - 600A

Advertising