Rockwell Automation 1492-CM1771-LD001 Digital I/O Conversion Module User Manual

Rockwell Automation Equipment

Advertising
background image

Digital I/O Conversion Module
(Cat 1492-CM1771-LD001)

I. Description

This Digital I/O Conversion system provides for the conversion of (1) 1771, 16 point I/O modules to be converted to (1)
1756, 16 point I/O module and consists of the following:

(1) 1771 Modules (16pt) to (1) 1756 Module (16pt)
(2) Conversion Modules: 1492-CM1771-LD001
(1) Cable: 1492-CONCAB005X (Table 2)
(1) Conversion Mounting Assembly: 1492-MUA… (Table 1)

This conversion is accomplished without the removal of any field wires from the existing 1771 Swing Arm. The existing
1771 Swing Arm fits directly onto the edge connector of the 1492 Conversion Module. On one end of the 1492 Cable
is (1) connector for the Conversion Module. On the other end is the Removable Terminal Block (RTB) for the 1756 I/O
module, as shown in the photo below. The I/O signals are routed through the 1492 Conversion Module and the 1492
Cable to the appropriate terminals on the 1756 I/O module per the Wiring Diagrams in Section V. As standard, both
portions of the 1492 Cables are 0.5M long, but we also offer a 1.0M cable length. Refer to the footnotes in Table 2,
Section III for further details.

PN-114270
DIR 10000060084 (Version 01)
Publication 1492-IN035B-EN-E

Printed in U.S.A.

Conversion Compatibility and
Product I.D. Label

25-Pin Connector for cable 1492-CONCAB005X

De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O
Chassis, and the power to the 1771 I/O Chassis itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING

1492-CM1771-LD001 Conversion Module

Advertising