Rockwell Automation 1336R REGEN 48,78,180A Precharge Contactor Repl. User Manual

Instructions

Advertising
background image

Instructions

1336 REGEN-5.14 May, 1998

1336 REGEN
48, 78 and 180A Precharge Unit
Precharge Contactor Replacement

This publication will guide you through the replacement of the Precharge
Contactor for 1336 REGEN Precharge Units.

Each 1336R-PRE-SP3A kit consists of:

• (1) 48/78A B/C Frame Precharge Contactor (PN 191113)

Each 1336R-PRE-SP4A kit consists of:

• (1) 180A D Frame Precharge Contactor (PN 191114)

ATTENTION:

This product and its associated equipment

contains ESD (Electrostatic Discharge) sensitive parts and
assemblies. Static control precautions are required when
installing, testing, servicing or repairing this assembly.
Component damage may result if ESD control procedures are
not followed. If you are not familiar with static control
procedures, reference publication 8000-4.5.2 "

Guarding Against

Electrostatic Damage

" or any other applicable ESD protection

handbook.

!

ATTENTION:

Electric Shock can cause injury or death. Remove

all power before working on this product.

For all 1336 REGEN Line Regeneration Packages, a separate 120VAC
user power supply is required.

Hazards of electrical shock exist if accidental contact is made with parts
carrying bus voltage. Before proceeding with any installation or
troubleshooting activity, allow at least one minute after input power has
been removed for the bus circuit to discharge. Bus voltage should be
verified by using a voltmeter to measure the voltage between the DC+
and DC– Converter Output Terminals. Do not attempt any servicing
until bus voltage has diminished to zero volts.

!

!

ATTENTION:

Only personnel familiar with the 1336 REGEN

Line Regen Package and associated equipment should plan or
implement the installation, start-up and subsequent maintenance
of the system. Failure to comply may result in personal injury
and/or equipment damage.