Rockwell Automation 1492-CM800-LD002 Field Wire Conv. Module for Modicon B804-116 to 1756-OA16 or B824-016 User Manual

Rockwell Automation Equipment

Advertising
background image

Field Wire Conversion Module for Modicon B804-116 to 1756-OA16 or
B824-016 to 1756-OB16E

(Cat 1492-CM800-LD002)

10000021853

(Version 00)

Printed in Germany

Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com.
In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog
Number and in the Search box type in the catalog number of the conversion system component.

I. Module Description

The 1492-CM800-LD002 conversion module provides field wire signal conversion from a Modicon® B804-116, 80 to
130Vac , 16-pt output module to a ControLogix 1756-OA16, 74 to 265Vac , 16-pt output module or a B824-016,
20 to 28Vdc, 16-pt output module to a 1756-OB16E, 10-31.2Vdc, 16-pt electronically fused output module. The
conversion module provides the mating connections to the B804-116 or B824-016 swing-arm (terminal block) with its
attached field wires. It routes those signals via its 20-pin connector and a 1492-CABLEX pre-wired cable to compat-
ible terminals of the 1756-OA16 or 1756-OB16E (refer to the Wiring Diagrams on pages 2 and 3 for details).

II. Module Installation

The 1492-CM800-LD002 conversion module must be installed in a 1492 conversion base-plate and cover-plate assem-
bly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion
assembly. For a list of compatible assemblies refer to Appendix A.

III. Conversion Module Compatibility Matrix

This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable

length is 003 (00.3 meters).

20-Pin Connector for 1492-CABLEX

Mating Connector for
B800 Terminal Block

Conversion Module

Compatible 800

Output Module

Compatible 1756

Output Module

Required 1492 Cable

1492-CM800-LD002

B804-116

1756-OA16

1492-CABLEX

1492-CM800-LD002

B824-016

1756-OB16E

1492-CABLEX

De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.

WARNING

1492-CM800-LD002 Conversion Module

Refer to conversion module Specifications Section: Maximum Operating Voltage