Rockwell Automation 1606-XLSRED Power Supply Reference Manual User Manual

Bulletin 1606 switched mode power supplies, Reference manual, Catalog number: 1606-xlsred index

Advertising
background image

Reference Manual

e

g

a

P

e

g

a

P

1. Intended Use .......................................................3
2. Installation Requirements...................................3
3. Input and Output Characteristics .......................4
4. Power Losses ........................................................5
5. Lifetime Expectancy and MTBF...........................6
6. Terminals and Wiring..........................................7
7. Functional Diagram.............................................8
8. Front Side and User Elements.............................8
9. EMC ......................................................................9

10. Environment ......................................................10
11. Protection Features ...........................................11
12. Safety Features ..................................................11
13. Dielectric Strength ............................................11
14. Certifications .....................................................12

15. Physical Dimensions and Weight ..................... 13
16. Accessories ........................................................ 14
17. Application Notes ............................................. 15

17.1. Recommendations for Redundancy .........15
17.2. Inductive and Capacitive Loads ................15
17.3. Example: 1+1 Redundancy up to 10A ......15
17.4. Example: N+1 Redundancy up to 30A .....16
17.5. Example: Battery Back-up ........................16
17.6. Example: Redundancy for Controls .........17
17.7. Example: Decoupling of Branches ...........18
17.8. Use in a Tightly Sealed Enclosure ............18
17.9. Mounting Orientations ............................19

Bulletin 1606 Switched Mode Power Supplies

Catalog Number: 1606-XLSRED

Index

PE and

symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol

.

Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.

T.b.d.—To be defined, value or description will follow later.

DC 24V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC
12V describes a 12V battery whether it is full (13.7V) or flat (10V)

24Vdc—A figure with the unit (Vdc) at the end is a momentary figure with no additional tolerance included.

may, shall, should—Three key words indicating, respectively: flexibility of choice with no implied preference, a mandatory requirement, flexibility of
choice with a strongly preferred implementation.

1+1 Redundancy—Use of two identical power supplies in parallel to provide
continued operation following most failures in a single power supply. The two
power supply outputs should be isolated from each other by using diodes or
other switching arrangements. E.g. two 10A power supplies are needed to
achieve a 10A redundant system.

N+1 Redundancy—Use of three or more identical power supplies in parallel
to provide continued operation following most failures in a single power supply.
All power supply outputs should be isolated from each other by using diodes or
other switching arrangements. E.g. to achieve a 40A redundant system, five 10A
power supplies are required in a N+1 redundant system.

Terminology and Abbreviations

N+1

Redundancy

1+1

Redundancy

AC

DC

AC

DC

AC

DC

AC

DC

AC

DC

AC

DC

IN 1

OUT

IN 2

IN 1

OUT

IN 2

IN 1

OUT

IN 2

Load

+

-

AC

DC

AC

DC

Load

+

-

IN 1

OUT

IN 2

Advertising
Table of contents