Rockwell Automation 1734-TBS_-TB3S_RTBS_RTB3S 1734-TB3 TB3S Installation Instructions User Manual

Point i/o wiring base assembly

Advertising
background image

Installation Instructions

POINT I/O Wiring Base Assembly

Catalog Numbers 1734-TBS, 1734-TB3S, 1734-RTBS, 1734-RTB3S

Environment and Enclosure

About the Assembly

Prepare the wires

The total wire size range for the RTBs is 22…14 AWG. The wire may be stranded or solid.

ATTENTION

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic

compatibility in residential and other environments due to

conducted and radiated disturbances.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed
for those specific environmental conditions that will be

present and appropriately designed to prevent personal injury

resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic.
The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may
contain additional information regarding specific enclosure type ratings that are required to comply with certain product
safety certifications.

In addition to this publication, see:

• Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements,

Allen-Bradley publication

1770-4.1.

• NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided

by different types of enclosure.

ATTENTION

Do not use wire ferrules on wires connected to the terminals on the modules.

Wire Size Range,
AWG

Number
of Wires

Strip Length

8-position RTB

12-position RTB

22…14 AWG

1

16

±1 mm (0.63±0.03 in)

14

±1 mm (0.55±0.03 in)

2

18

±1 mm (0.71±0.03 in)

16

±1 mm (0.63±0.03 in)

Mounting Base

Removable
Terminal Block
(RTB)

RTB Removal
Handle

Mechanical Keying

(orange)

Interlocking Side

Pieces

DIN Rail Locking

Screw (orange)

44895

1734-TB3 shown

Strip Length

1

5

5

9

4

-

N

P

9

0

0

2

e

n

u

J

-

P

-

N

E

-

B

3

1

0

N

I

-

4

3

7

1

n

o

i

t

a

c

il

b

u

P

Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.

Additional Resources

You can view or download publications at

http://www.literature.rockwellautomation.com

. To order

paper copies of technical documentation, contact your local Rockwell Automation distributor or sales
representative.

Signal terminal current, max

1734-RTBS and 1734-RTB3S: 2A

Isolation voltage

250V, Basic Insulation Type, field-side to system

Type tested at 1000V AC for 60 s

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Groundi

ng

Guidelines, publication

1770-4.1 .

Environmental

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Certifications (1734-TB3 and 1734-TB3S only)

Certification (when product

is marked)

(1)

Value

c-UR-us

UL Recognized Component Industrial Control Equipment, certified for US and Canada.

See UL File E195367.

:

h

t

i

w

t

n

a

il

p

m

o

c

,

e

v

i

t

c

e

r

i

D

C

M

E

C

E

/

8

0

1

/

4

0

0

2

n

o

i

n

U

n

a

e

p

o

r

u

E

E

C

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

European Union 2006/95/EC LVD, compliant with:

EN 61131-2; Programmable Controllers (Clause 11)

C-Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR11; Industrial

Emissions

(1)

See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.

General

Attribute

Value

Advertising