Installing the Module

2-13

Unshielded Connector Grounding Requirements

When using twisted pair network wiring with unshielded
AK-U0-RJ45-TB2P connectors, ground the RJ45 socket on the drive by
connecting the drive chassis ground power terminal to the I/O block
shield terminal.

The 1769-SM2 module’s RJ45 connectors (CH1, CH2, and CH3), which
are electrically common, should be grounded by attaching a drain wire
from the 1769-SM2 terminal block (item 11 in

Figure 1.1

) to a grounded,

conductive surface (i.e. metal panel). If shielded cable (not required) is
used, the cable shield should also be connected to the chassis by
attaching the cable shield to the 1769-SM2 terminal block (

Figure 2.7

).

Good wiring practice dictates that the cable shield be terminated to the
chassis at only one point along the cable to prevent ground loops from
occurring. The chassis terminal block on the 1769-SM2 module is
provided as a convenient place for this termination.

Figure 2.7 Unshielded Connector Grounding Details

Drive

Drive I/O Block

PowerFlex 4

Terminal 16

PowerFlex 4M

Terminal 16

PowerFlex 40

Terminal 19

PowerFlex 40P

Terminal 19

PowerFlex 400

Terminal 20

DSI / Modbus RTU

MODULE

CH1

CH2

CH3

C

H

1

C

H

2

C

H

3

To Drive 1

To Drive 2

. . .

To Drive 1

To Drive 2

. . .

To Drive 1

To Drive 2

. . .