PanelView Plus and PanelView Plus CE Terminals to Logix Controllers

PanelView Plus Terminals to Communication Adapters

Cables: PanelView Plus and PanelView Plus CE to Logix Controllers

Protocol

PanelView Plus Comm Port

ControlLogix

CH0 (9-pin RS-232)

(DF1)

CompactLogix

CH0 (9-pin RS-232)

(DF1 or DH-485)

DF1

(any)

RS-232 (DF1) Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

DH-485
(any)

RS-232 (DH-485) Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C

N/A

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

DH-485 Port
PanelView Plus 400 and 600
2711P-RN3

(2)

,

PanelView Plus 700 to 1500
2711P-RN6, -RN6K

(2)

For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).

N/A

Use AIC+ Module

(1761-NET-AIC)

Connect to Port 3

ControlNet

ControlNet Port
PanelView Plus 400 and 600
2711P-RN15C
PanelView Plus 700 to 1500
2711P-RN15S, -RN15SK

Use 1756-CNB Module with ControlNet Cable

1769-L35CR, -L32C, -1768-CNB, or 1768-CNBR

with ControlNet Cable

DeviceNet

(1)

(1)

DeviceNet and Remote I/O communication modules are no longer available. Cable information is provided for reference only.

DeviceNet Port
PanelView Plus 400 and 600
2711P-RN10C
PanelView Plus 700 to 1500
2711P-RN10H

Use 1756-DNB Module

with DeviceNet Cable

Use 1769-SDN Module

with DeviceNet Cable

EtherNet/IP

EtherNet/IP Port
PanelView Plus 400 to 1500
All except 2711P-xxx5xx

Use 1756-EN2T or 1756-ENBT Module with

1585J-M Type Cable or

2711P- CBL-EX04 (4 m/14 ft)

(3)

(3)

For a direct connection between the terminal and controller, use the 2711P-CBL-EX04 crossover cable.

To 1769-L35E, L23E, L32E,

or 1768-ENBT Module with 1585J-M Type Cable

or 2711P- CBL-EX04 (4 m/14 ft)

(3)

Remote I/O

(1)

Remote I/O Port
PanelView Plus 400 to 1500
2711P-RN1, 2711P-RN6

Use 1756-DHRIO Module

with

Shielded Twinaxial Cable (1770-CD)

N/A

DH+

DH+ Port
PanelView Plus 400 and 600
2711P-RN8
PanelView Plus 700 to 1500
2711P-RN6, -RN6K

Use 1756-DHRIO Module

with

Shielded Twinaxial Cable (1770-CD)

N/A

Cables: PanelView Plus to Communication Adapters

Protocol

PanelView Plus Comm Port

1747-AIC

1761-NET-AIC

Port 1 (9-pin)

Port 2

8-pin Mini DIN()

Port 3

(DH-485)

1761-NETDNI

or 1771-NET-ENI

DF1 (any)

RS-232 Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C (for 400 and 600)

N/A

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft)

N/A

1761-CBL-AP00 (5 m)

1761-CBL-PM02 (2 m)
2711-CBL-PM05 (5 m)

2711-CBL-PM10 (10 m)

DH-485
(any)

RS-232 Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C (for 400 and 600)

N/A

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

2711-NC21 (5 m/16 ft)

2711-NC22 (15 m/49 ft)

N/A

DH-485 Port
PanelView Plus 400 and 600
2711P-RN3

(1)

1747-C10 (2 m/6ft)

1747-C11 (0.3 m/1 ft)

1747-C20 (6 m/20 ft)

N/A

1761-CBL-AS03

(3 m/10 ft)

1761-CBL-AS09

(9 m/30 ft)

to single AIC+

N/A

DH-485 Port
PanelView Plus 700 to 1500
2711P-RN6, -RN6K

Direct Connection to

Single AIC with

Belden 9842 Cable

(2)

N/A

Direct Connection to

Single AIC+ with

Belden 9842 Cable

(2)

N/A

(1)

For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).

(2)

Use serial port on the PanelView Plus terminal with an AIC+ module for a DH-485 network solution.