Modem Connection

Wire or radio modem communication is possible between the
terminal and controller. Each modem must support full duplex
communication. Refer to your modem user manual for details on
settings and configuration.

Construct a Null Modem Cable

To construct a null modem cable, refer to this pinout.

Null Modem Pinout

PanelView
Plus 9-pin

9-pin
Modem

PanelView
Plus 9-pin

25-pin
Modem

FG (Frame Ground)

-

-

-

1

FG

TD (Transmit Data)

3

2

3

3

RD

RD (Receive Data)

2

3

2

2

TD

RTS (Request to Send)

7

8

7

5

CTS

CTS (Clear to Send)

8

7

8

4

RTS

SG (Signal Ground)

5

5

5

7

SG

DSR (Data Set Ready)

6

4

6

20

DTR

DTR (Data Terminal Ready)

4

6

4

6

DSR

PanelView Plus Terminal

DF1 Port

Modem

Modem

Optical Isolator

Controller