Chapter 7 Terminal Connections

DH-485 Network Port Wiring for 700 to 1500 Terminals

Use these instructions for wiring Belden cable. If you are using
standard Allen-Bradley cables, see the

Logic Controller Cable Charts

.

RS-485 Connector to the Communication Cable

Attach the connector to the Belden #3106A or #9842 Cable as shown.

The table shows connections for Belden #3106A.

Belden 3106A Wire Connections

IMPORTANT

A daisy-chained network is recommended. We do not
recommend hybrid star/daisy chain networks as shown.

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue

Blue

Terminal 3 - (Common)

White/Orange

White with Orange Stripe

Terminal 4 - (Data B)

Orange with White Stripe

Terminal 5 - (Data A)

Belden
#3106A or
#9842

Belden
#3106A or
#9842

Belden
#3106A or
#9842

Connector

Connector

Connector

Incorrect

Orange with White Stripes

White with Orange Stripes

Shrink Tubing
Recommended

Blue (#3106A) or
Blue with White Stripes (#9842)

Drain Wire

6 Terminal
5 A
4 B
3 Common
2 Shield
1 Chassis Ground

Single Cable Connection

to Previous Device

to Successive Device

Multiple Cable Connection