Dh+ network connections – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 180

Advertising
background image

180

Publication 2711P-UM001J-EN-P - November 2009

Chapter 7 Terminal Connections

DH+ Network Connections

Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD),
to connect a terminal to a DH+ link.

You can connect a DH+ link in two ways.

Trunk line/drop line - from the drop line to the connector screw
terminals on the DH+ connectors of the processor

Daisy chain - to the connector screw terminals on the DH+
connectors on the processor

Follow these guidelines when installing DH+ communication links.

do not exceed these cable lengths:

Trunk line-cable length: 3,048 m (10,000 ft).

Drop-cable length: 30.4 m (100 ft).

The maximum cable length is determined by baud rate.

Do not connect more than 64 stations on a single DH+ link.

PanelView Plus 400-1500

82

Ω

terminating resistor for

230.4 Kbps

150

Ω

terminating resistor for

57.6 Kbps and 115.2 Kbps

To Controller

Terminating Resistor

DH+ Port on Communication Module

Clear 1

Shield SH 2

Blue 3

Belden