Remote i/o connections – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 181

Advertising
background image

Publication 2711P-UM001J-EN-P - November 2009

181

Terminal Connections Chapter 7

Remote I/O Connections

Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD),
to connect a terminal to a Remote I/O scanner. The maximum cable
length (link distance) is determined by the baud rate.

2800 m (10,000 ft) for 57.6 Kbps

1400 m (5,000 ft) for 115.2 Kbps

700 m (2,500 ft) for 230.4 Kbps

See Industrial Automation Wiring and Grounding Guidelines,
publication

1770-4.1

. The user manual for the I/O scanner module

also provides cabling information.

PanelView Plus 700 to 1500 Terminals

PanelView Plus 400 and 600 Terminals

82

Ω

terminating resistor for 230.4 Kbps

150

Ω

terminating resistor for 57.6 Kbps

and 115.2 Kbps

82

Ω

terminating resistor for 230.4 Kbps

150

Ω

terminating resistor for 57.6 Kbps

and 115.2 Kbps

Belden

To Controller

To Controller

Terminating Resistor

Terminating Resistor

Clear 1

Shield SH 2

Blue 3

Clear 3

Shield SH 2

Blue 1

Belden

Remote I/0 Port on Communication Module

Remote I/0 Port on Communication Module