Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 38

Advertising
background image

38

Publication 2711P-UM001J-EN-P - November 2009

Chapter 2 Installation

6. Insert all mounting levers into the mounting slots on the

terminal.

Slide each lever until the flat side of the lever touches the
surface of the panel.

7. When all levers are in place, slide each lever an additional notch

or two until you hear a click.

8. Rotate each lever in the direction indicated until it is in the final

latch position.

Follow the latching sequence for the optimum terminal fit.

Use this table as a guide to provide an adequate gasket seal
between the terminal and the panel.

Mounting Slots

Mounting Levers

Flat Side of Lever

Notch

6

1

Alignment Marks

Rotate lever until notch in
lever aligns with proper
alignment mark on terminal.

6 Levers

2

4

6

5

1

3

1

4

3

2

4 Levers

Lever Position

Panel Thickness Range

Typical Gauge

1

1.5…2.01 mm (0.060…0.079 in.)

16

2

2.03…2.64 mm (0.08…0.104 in.)

14

3

2.67…3.15 mm (0.105…0.124 in.)

12

4

3.17…3.66 mm (0.125…0.144 in.)

10

5

3.68…4.16 mm (0.145…0.164 in.)

8/9

6

4.19…4.75 mm (0.165…0.187 in.)

7

Terminal
Markings

1

2

3

4

5

6

ATTENTION

Follow instructions to provide a proper seal and to
prevent potential damage to the product. Rockwell
Automation assumes no responsibility for water or
chemical damage to the terminal or other equipment
within the enclosure because of improper installation.

Advertising