Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 52

Advertising
background image

52

Publication 2711P-UM001J-EN-P - November 2009

Chapter 3 Power Connections

External Power Supply For Non-insolated DC Terminals

Use a single, 24V DC power supply to power each PanelView Plus
device, such as cat. no. 2711P-RSACDIN. Using a separate, isolated
and ungrounded source to power each terminal prevents ground loop
currents from damaging the terminals.

The output on the power supply must be isolated from the input and
not connected to earth/ground.

The non-isolated power supply does not provide galvanic isolation. A
Class 2 or Safety Extra-Low Voltage (SELV) isolated power supply with
a 24V DC nominal output voltage is required to power the terminal.

Multiple AC Power Supplies to Power Multiple DC Terminals

TIP

To identify non-isolated DC logic modules refer to the

Logic

Modules (700 to 1500 only)

table on

page 24

.

TIP

All 400 and 600 DC terminals contain non-isolated DC power
supplies.

ATTENTION

Use a Class 2 or SELV supply as required by local wiring
codes for your installation. The Class 2 and SELV power
sources provide protection so that under normal and
single-fault conditions, the voltage between the conductors,
and between the conductors and functional earth or
protective earth does not exceed a safe value.

Circuitry

Circuitry

dc+

PanelView Plus

PanelView Plus

AC/DC Power Supply

L1

L2

dc-

dc+

dc-

L1

L2

(2711P-RSACDIN)

(2711P-RSACDIN)

AC/DC Power Supply