Power Connections Chapter 3

Functional Earth Connection

The PanelView Plus 700 to 1500 devices with an AC power input also
have a functional earth connection on the back of the display.

The functional earth terminal requires a minimum wire gauge.

Functional Earth Wire Specifications for AC Power

IMPORTANT

On 700 to 1500 devices, you must connect both protective earth
and functional earth to ground.

Terminal

FE Symbol

Wire Type

Wire Gauge

Terminal Screw Torque

700 to 1500

GND

Stranded or solid

Cu 90 °C (194 °F)

14…10 AWG

1.13…1.36 Nm (10…12 lb•in)

ATTENTION

The functional earth and protective earth connections to ground
are mandatory. The functional earth is required for
Electromagnetic Compliance (EMC) with the European Union
(EU) EMC directive for CE-mark conformance. The protective
earth/ground connection is required for safety and regulatory
compliance.