Rockwell Automation Publication 6181P-UM003A-EN-P - May 2014

Chapter 2

Installation

Mounting Clearance
Requirements

Figure 6 - Minimum Clearances

Computer Dimensions

Review computer dimensions to estimate the clearance necessary for computer
installation. Dimensions are given in mm (in.).

Figure 7 - Non-display Computer

IMPORTANT

Because of self-heating, do not operate the computer in an enclosure with the
minimum clearances unless adequate ventilation or other cooling methods are
used to lower the temperature within the enclosure.

Allow enough clearance to easily install or remove internal drives, optical discs,
cables, and peripheral components.

Right and left are based on facing the front of the computer.

Item

Description

Value

1

Top

50 mm (2 in.)

2

Left (for airflow)

50 mm (2 in.)

3

Rear

50 mm (2 in.)

4

Right (for airflow and drive access)

127 mm (5 in.)

5

Bottom (for I/O port access and ventilation)

102 mm (4 in.)

2

1

3

4

5

3.4

(0.13)

100.7 (3.96)

67.7 (2.67)

16.4
(0.65)

16.4

(0.65)

320.2 (12.61)

335.3 (13.2)

87.1

(3.43)

87.1

(3.43)

87.1

(3.43)

190.5

(7.5)

251

(9.88)