Commissioning Your Ultra3000 Drive

61

9. Determine if your test completed successfully.

If

Then

Your test completes successfully, this dialog appears.

1. Click OK.

2. Remove Drive Enable signal (CN1-31).

3. Go to Tune Your Axis.

Your test failed, this dialog appears.

1. Click OK.

2. Verify that the main three-phase bus power is up.

3. Verify that the Drive Enable signal (CN1-31) is

applied to the axis you are testing.

4. Verify conversion constant entered in the

Conversion tab.

5. Return to step 6 and run the test again.