Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual

Page 135

Advertising
background image

Publication 2093-UM001A-EN-P — March 2007

Troubleshooting the Kinetix 2000 Drive System

135

E05

DriveOvercurrent
Fault

(Power Fault)

Self-protection of the
Intelligent Power Module
(IPM) is indicating a major
power related fault
condition

Motor cables shorted.

Verify continuity of motor power cable and
connector.

Motor winding shorted internally.

Disconnect motor power cables from the
motor. If the motor is difficult to turn by
hand, it may need to be replaced.

Kinetix 2000 drive temperature too high.

• Check for clogged vents or defective

fan.

• Make sure cooling is not restricted by

insufficient space around the unit.

Operation above continuous power rating
and/or product environmental ratings.

• Verify ambient temperature is not too

high.

• Operate within the continuous power

rating.

• Reduce acceleration rates.

Kinetix 2000drive has a short circuit,
overcurrent, or failed component.

Remove all power and motor connections,
and preform a continuity check from the dc
bus to the U, V, and W motor outputs. If a
continuity exists, check for wire fibers
between terminals, or send drive in for
repair.

E06

HardOvertravel
Fault

(+/- Hard Overtravel)

Axis moved beyond the
physical travel limits in the
positive/negative direction

Dedicated overtravel input is inactive.

• Check wiring.
• Verify motion profile.
• Verify axis configuration in software.

E07

MotFeedbackFault

(Motor Feedback Loss)

The feedback wiring is open, shorted, or missing.

• Check motor encoder wiring.
• Run Hookup test in RSLogix 5000

software.

E09

BusUndervoltage
Fault

(Bus Undervoltage)

With three-phase power
present, the dc bus voltage
is below its limit

DC bus voltage for 230V system is below
137V

• Verify voltage level of the incoming ac

power.

• Check ac power source for glitches or

line drop.

• Install an uninterruptible power supply

(UPS) on your ac input.

DC bus voltage fell below
the undervoltage limit
while an axis on the
follower power rail was
enabled

Disable follower axis before removing
power.

E10

DriveOvervoltage
Fault

(Bus Overvoltage)

The dc bus voltage is
above its limit

Excessive regeneration of power.

When the motor is driven by an external
mechanical power source, it may
regenerate too much peak energy
through the drive power supply. The
system faults to save itself from an
overload.

• Change the deceleration or motion

profile.

• Use a larger system (motor and

Kinetix 2000 drive).

• Install shunt module.

DC bus voltage for 230V system is over
410V

Verify input is within specifications.

E11

MotFeedbackFault

(Illegal Hall State)

State of Hall feedback
inputs is incorrect

Bad connections.

• Verify the Hall wiring at the MF

connector on the IAM/AM.

• Verify 5V power supply to the encoder.

E16

Softovertravel
Fault

(+/- Software
Overtravel)

Axis position exceeded maximum software setting.

• Verify motion profile.
• Verify overtravel settings are

appropriate.

Error
Code

Fault Message
RSLogix
(HIM)

Problem or Symptom

Potential Cause

Possible Resolution