Troubleshooting the Kinetix 2000 Drive System

E67

DriveHardFault

(Task init)

Operating system failed

Software initialization fault detected due
to hardware failure.

• Cycle power.
• If fault persists, replace module.

E68

DriveHardFault

(SCANport Comm)

DPI communication failed

The DPI device or cable is faulty.

Check DPI connections.

E69

DriveHardFault

(Objects Init)

Non-volatile memory is corrupt due to control board hardware failure.

Load default parameters, save to
non-volatile memory, and recycle power or
reset the drive.

E70

DriveHardFault

(NV Mem Init)

Non-volatile memory is corrupt due to control board software error.

Load default parameters, save to
non-volatile memory, and recycle power or
reset the drive.

E71

DriveHardFault

(Memory Init)

RAM or Flash memory validation failure

• Cycle power.
• If fault persists, replace module.

E72

DriveOvertemp
Fault

(Drive Overtemp)

Inverter thermal switch
tripped

The fan on the IAM or an AM failed.

Replace the failed module.

The cabinet ambient temperature is
above rating.

Check the cabinet temperature.

The machine duty cycle requires an RMS
current exceeding the continuous rating
of the controller.

Change the command profile to reduce
speed or increase time.

The airflow access to the Kinetix 2000
system is limited or blocked.

Check airflow and re-route cables away
from the Kinetix 2000 system.

E73

Communicate

(Backplane Comm)

Power rail CAN communications failed.

Check module for proper mount.

Power rail connection shorted or open.

Check power rail and module for foreign
objects.

E74

DriveOvercurrent
Fault

(Bus OverCurrent)

DC link current exceeds
rating

Motor or transmission malfunction.

• Check for proper motor sizing.
• Check/replace transmission device.
• Check/replace motor.

IAM not properly sized.

• Check for proper IAM sizing.
• Install larger kW rated IAM.

E75

DriveOvervoltage
Fault

(Shunt Time Out)

The IAM, AM, or SM has exceeded its shunt resistor continuous rating.

• Use a properly sized shunt or modify

duty cycle of the application.

• System uses internal shunt and

requires external shunt for additional
capacity.

E76

DriveHardFault

(CAN Init)

DPI hardware initialization
fault detected

Control board hardware failure.

• Reset System.
• If fault persists, replace system

module.

E78

DriveHardFault

(SERCOS Init)

Control hardware fault detected.

• Cycle power.
• If fault persists, replace module.

E79

DriveOvervoltage
Fault

(Shunt Module Flt)

Shunt module temperature fault LED indicator is steady red.

Refer to Temperature Fault LED Indicator
on page 141.

Shunt module shunt fault LED indicator is steady red.

Refer to Shunt Fault LED Indicator on page
141.

Module missing from power rail.

• Install missing module on power rail.
• Fill empty slot with slot filler module.

E80

DriveHardFault

(CPLD Flt)

Control hardware fault detected.

Replace module.

Error
Code

Fault Message
RSLogix
(HIM)

Problem or Symptom

Potential Cause

Possible Resolution