Iam/am status indicators, Iam/am status indicators o – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual

Page 139

Advertising
background image

Publication 2093-UM001A-EN-P — March 2007

Troubleshooting the Kinetix 2000 Drive System

139

IAM/AM Status Indicators

Drive Status LED Indicator

Comm Status LED Indicator

Bus Status LED Indicator

E81

DriveHardFault

(Common Bus Flt)

Follower IAM detected ac input power being applied.

Remove ac input power connections from
follower IAM.

E90

DriveHardFault

(Pre-charge Timeout Flt)

Pre-charge resistor power exceeds the resistor rating.

Allow resistor to cool.

All

others

RESERVED

Call your local Rockwell Automation sales
representative.

Error
Code

Fault Message
RSLogix
(HIM)

Problem or Symptom

Potential Cause

Possible Resolution

Drive Status LED
Indicator

Status

Potential Cause

Possible Resolution

Off

Normal, no faults

N/A

N/A

Steady Red

Drive faulted

Seven-segment Fault Status display shows an
error code

Fault exists, refer to Seven-segment LED
Indicator Error Codes begi
nning on page 134.

Comm Status LED
Indicator

Status

Potential Cause

Possible Resolution

Steady Green

Communication ready

No faults or failures.

N/A

Flashing Green

Establishing
communication

System is still in the process of establishing
SERCOS communication.

Wait for steady green LED indicator.

Node address setting on the drive module
does not match SERCOS controller
configuration.

Verify proper node switch setting.

Off

No communication

(1)

Loose fiber-optic connection.

Verify proper fiber-optic cable connections.

Broken fiber-optic cable.

Replace fiber-optic cable.

Receive fiber-optic cable connected to
SERCOS transmit connector and vice versa.

Check proper SERCOS fiber-optic cable
connections.

(1)

Refer to Fiber-optic Cable Installation and Handling Instructions, publication 2090-IN010, for more information.

Bus Status LED
Indicator

Status

Condition

Steady Green

Bus power is present, axis enabled.
No faults or failures.

Normal when:

• 24V is applied to Hardware Enable Input (IOD/AF-43).
• MSO instruction is commanded in RSLogix 5000 software.