Troubleshooting the Kinetix 2000 Drive System

SM Status Indicators

Each of the shunt module LED indicators provide specific troubleshooting
information.

General Shunt Module Troubleshooting

Flashing Green

Bus power is present, axis disabled.
No faults or failures.

Normal when:

• 24V is not applied to Hardware Enable Input (IOD/AF-43).
• MSO instruction is not commanded in RSLogix 5000 software.

Off

Bus power not present.

• Normal when bus power is not applied.
• Fault exists, refer to Seven-segment LED Indicator Error Codes section beginning

on page 134.

Bus power is present in follower IAM.

• Follower IAM is not configured as CommonBus Follow in RSLogix 5000

software.

• After dc bus voltage is applied, a 2.5 second delay before the LED indicator

begins flashing green is normal operation to provide common bus leader time to
complete pre-charge.

Bus Status LED
Indicator

Status

Condition

Module

Status

Under These Conditions

SM

Fault is latched

Until fault condition is corrected and cleared.

Fault is cleared

• Using RSLogix MASR, MAFR, MGSR commands or the HIM (red

stop button).

• Only after the dc bus is discharged (SM Bus Status LED indicator is

flashing).

• Drive must be configured with 2093-ASP06 or Bulletin 1336

external shunt resistor.

IAM/AM

Disabled (for dc bus
regulation)

• When the 2093-ASP06 shunt module is used on a 230V system.
• When a 230V system is configured with a Bulletin 1336 external

shunt resistor.

• When configured in Common Bus Follower mode.

Enabled to discharge the dc
bus

Drive (IAM or leader IAM) three-phase power is removed.

Disabled from discharging
the dc bus

When configured in common bus follower mode.

IMPORTANT

Under some fault conditions, two reset commands may be required to
clear drive and SM faults.