Troubleshooting the Kinetix 2000 Drive System

141

Bus Status LED Indicator

Temperature Fault LED Indicator

Shunt Fault LED Indicator

All SM Status LED Indicators

Bus Status LED
Indicator

Status

Potential Cause

Possible Resolution

Flashing

Normal condition when control power is applied and bus voltage is less than
60V dc.

N/A

Steady Green

Normal condition when control power is applied and bus voltage is greater
than 60V dc.

N/A

Off

Control power is not present.

Internal power supply failure.

Replace shunt module.

Temp Fault LED
Indicator

Status

Potential Cause

Possible Resolution

Off

Normal condition

N/A

Steady Red

SM internal temperature
exceeds operating
temperature specification

Shunt module fan failed

Replace shunt module.

Shunt module temperature exceeds rating

• Allow shunt module to cool.
• Reset faults.
• Verify IAM bus regulator configuration.

External over temperature
condition

External temperature switch is open

• Allow shunt module to cool.
• Reset faults.
• Verify IAM bus regulator configuration.

TS jumper is not present

Install jumper.

Shunt Fault LED
Indicator

Status

Potential Cause

Possible Resolution

Off

Normal condition

N/A

Steady Red

Shorted internal or external
shunt resistor

Mis-wired shunt jumper or other short on RC
connector

• Correct mis-wire (shorted) condition.
• If problem persists, replace shunt module.

Mis-wired (shorted) external shunt wiring

SM Status LED
Indicator

Status

Potential Cause

Possible Resolution

• Bus Status
• Temperature Fault
• Shunt Fault

All three SM status LED
indicators flash
simultaneously

Shunt module hardware failure

• Cycle power.
• If problem persists, replace shunt module.