Typical DC Common Bus System Installation

In the example above, a leader IAM is connected to a follower IAM via the dc
common bus. When planning your panel layout, you must calculate the total
bus capacitance of your dc common bus system to correctly size the leader
IAM to pre-charge the entire system. In RSLogix5000 software you identify
the common bus follower (disabling its shunt capabilities), and in doing so
require the leader IAM to control the entire common dc bus.

Refer to Appendix D, beginning on page 209, for more information.

1 2 3

1 2

1 2 3

1 2

SERCOS interface

Tx (rear)

Rx (front)

OK

CP

Logix SERCOS Interface Module

Logix Chassis
(ControlLogix is shown)

Logix Controller Programming Network

Workstation with

RSLogix 5000 Software

Common Bus

Line Interface Module

(optional component)

2094-AL

xx

S

Line Filter

2090-XXLF-

xxxx

SERCOS Fiber-optic Ring 2090-SC

xxx-x

Kinetix 2000 Multi-axis Servo Drive System

Integrated

Axis

Module

(IAM)

Shunt Module
and
Slot Filler Module
(Required when slot
is unoccupied by an
IAM, AM, or Shunt.)

Power

Rail

Bonded Cabinet
Ground Bus

SERCOS

Fiber-optic Ring

2090-SC

xxx-x

Axis Modules (4x)

Integrated

Axis

Module

(IAM)

Shunt Module (optional component)

Slot Filler Module
(Required when slot
is unoccupied by an
IAM, AM, or Shunt.)

Power

Rail

Bonded Cabinet
Ground Bus

Axis Modules (4x)

170...264V ac

Single-phase

or Three-phase

Input Power

170...264V ac
Single-phase
Control Power

170...264V ac

Single-phase

Control Power

Common

Bus

Fusing

IMPORTANT

If total bus capacitance of your system exceeds the leader IAM
pre-charge rating and input power is applied, the IAM seven-segment
Fault Status LED indicator will display error code E90 (pre-charge
timeout fault). To correct this condition, you must replace the leader
IAM with a larger module or decrease the total bus capacitance by
removing axis modules.